PORTABLE CT PT ANALYZER

PORTABLE CT PT ANALYZER

Model No.︰GF106T

Brand Name︰GFUVE

Country of Origin︰China

Unit Price︰US $ 1 / SET

Minimum Order︰1 SET

Inquire Now

Product Description

GF106T PORTABLE CT PT ANALYZER

It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

MAIN FUNCTIONS

I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity 
4. 5% and 10% error curve 4. Withstand test of power frequency alternating current
5. Current Injecting 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Withstand test of power frequency alternating   current 7. Actual secondary load test 
8. Automatic calculation of excitation knee 
point value
8. Resistance test
9. Actual secondary load test 
10. Resistance test 

PARAMETERS

Electrical parameters
Accuracy 0.2%, 0.5%
Power supply AC 220V±10% or AC 110V±10%, 50/60Hz
Excitation voltage output 0-2500Vrms, 
Excitation current output 0-5Arms (20A peak-value)
Large current output 0-1000A
Electrical parameters - continued
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurement Range 0.1-300Ω
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurement Accuracy ±4min
Resolution 0.01min
CT ratio error measurement Range ≤25000A/5A(5000A/1A)
Accuracy ≤0.5%
PT ratio error measurement Range 1-500KV
Accuracy ≤0.5%
Standards 
Reference standards GB1207-2006, GB1208-2006, GB16847-1997 
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm) 400 x 250 x 250 
Weight (kg)   ≤22
Environmental conditions 
Relative humidity    90RH%
Operating temperature -10°C to +40°C
Altitude ≤1000m

Payment Terms︰ L/C, T/T, western union